Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY IDENTIFY PANEL DIRECTORYS-NEC 408.4 2) NEED PROPER WORKING CLEARANCE PANEL "H E" NEC 110.26 3) NEED 40 AMP BREAKER A/C UNIT #25 4) PIG TAIL GROUNDS WITH #10 CU TO AC UNITS 5) PARTIAL INSPECTION, STILL NEED TO INSPECT CEILING |