Permit: T07CM03019

Parcel: 105102420


Addresses:

455 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03019

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/19/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROPERLY IDENTIFY PANEL DIRECTORYS-NEC 408.4
2) NEED PROPER WORKING CLEARANCE PANEL "H E" NEC 110.26
3) NEED 40 AMP BREAKER A/C UNIT #25
4) PIG TAIL GROUNDS WITH #10 CU TO AC UNITS
5) PARTIAL INSPECTION, STILL NEED TO INSPECT CEILING