Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH 2. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL 3. PANEL NOT GROUNDED 4. TIGHTEN LOCK NUTS ON CONNECTORS @ PANEL 5. NEED PROTECTIVE BUSHINGS ON CONDUCTORS #4 & LARGER 6. PANEL DIRECTORY @ DISTRIBUTION PANEL 7. PROPERLY CONNECT GROUNDS @ DISTRIBUTION PANEL NO WASHERS & TECH SCREWS 8. RECEPTACLES WITH NO POWER & NO GROUND |