Permit: T07CM03018

Parcel: 12809005E


Addresses:

5353 E 22ND ST 01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03018

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. HAVE REVISED DRAWINGS AT FINAL
2. WILL CHECK ATTIC AT FINAL
3. OK WALLS & CEILINGS
10/15/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND ALL METAL BOXES
2. INSTALL MISSING MUD RINGS
3. USE BOXES LISTED FOR CEILING FANS
4. BRING OUT BOXES GO FLUSH WITH FINISHED SURFACE
MAX 1/4" BACK
5. STRAP MC CABLE WITHIN 12" OF BOXES & PANELS
6. STRAP MC CABLE IN ATTIC WITHIN 12" OF LIGHTS, BOXES AND EVERY 6' BETWEEN
7. PROVIDE LIGHT & RECEPTACLE FOR SERVICE AT AC EQUIPMENT
8. NEED REVISION TO PLANS FOR ALL WORK DONE
9. NEED TO PROTECT CABLES WITHIN 6' OF ATTIC ACCESS
10. STRAP PVC IN ATTIC
11. CANNOT USE PLASTIC BOXES WITH METALLIC WIRING
(MC CABLE)
12. TWIST GROUNDS TOGETHER & USE PROPER CRIMP TOOL WHEN USING BARREL CRIMPS
13. NAIL PLATE CABLES WITHIN 1 1/4" FROM BURIED HOLE TO FACE OF STUD
14. NEED 1 1/4" ON CABLES PARALLEL WITH FRAMING MEMBERS