Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03018
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. HAVE REVISED DRAWINGS AT FINAL 2. WILL CHECK ATTIC AT FINAL 3. OK WALLS & CEILINGS |
|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ALL METAL BOXES 2. INSTALL MISSING MUD RINGS 3. USE BOXES LISTED FOR CEILING FANS 4. BRING OUT BOXES GO FLUSH WITH FINISHED SURFACE MAX 1/4" BACK 5. STRAP MC CABLE WITHIN 12" OF BOXES & PANELS 6. STRAP MC CABLE IN ATTIC WITHIN 12" OF LIGHTS, BOXES AND EVERY 6' BETWEEN 7. PROVIDE LIGHT & RECEPTACLE FOR SERVICE AT AC EQUIPMENT 8. NEED REVISION TO PLANS FOR ALL WORK DONE 9. NEED TO PROTECT CABLES WITHIN 6' OF ATTIC ACCESS 10. STRAP PVC IN ATTIC 11. CANNOT USE PLASTIC BOXES WITH METALLIC WIRING (MC CABLE) 12. TWIST GROUNDS TOGETHER & USE PROPER CRIMP TOOL WHEN USING BARREL CRIMPS 13. NAIL PLATE CABLES WITHIN 1 1/4" FROM BURIED HOLE TO FACE OF STUD 14. NEED 1 1/4" ON CABLES PARALLEL WITH FRAMING MEMBERS |