Permit: T07CM03017

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Permit Number - T07CM03017

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2008 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
100 PSI TEST ON NORTH STEAM PIPING
OK TO INSULATE
07/09/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
100 PSI TEST ON STEAM PIPING SOUTH PART OF SUITE OK TO INSULATE. NORTH PART NOT HOLDING PRESSURE.
HARD LIDS OK FOR SHEETROCK
06/18/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
CHILLED WATER SUPPLY & RETURN LINES 130 PSI TEST
UP TO ROOF - OK TO INSULATE & LABEL PIPES
06/12/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
125 PSI TEST ON HOT WATER PIPING ON ROOF & 3RD FLOOR
OK TO INSULATE