Inspection History: MECHANICAL - PROGRESS
Permit Number - T07CM03017
Inspection Description - MECHANICAL - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2008 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection :* 100 PSI TEST ON NORTH STEAM PIPING OK TO INSULATE |
|
07/09/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 100 PSI TEST ON STEAM PIPING SOUTH PART OF SUITE OK TO INSULATE. NORTH PART NOT HOLDING PRESSURE. HARD LIDS OK FOR SHEETROCK |
|
06/18/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* CHILLED WATER SUPPLY & RETURN LINES 130 PSI TEST UP TO ROOF - OK TO INSULATE & LABEL PIPES |
|
06/12/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 125 PSI TEST ON HOT WATER PIPING ON ROOF & 3RD FLOOR OK TO INSULATE |