Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIEMENS BQD BREAKER NOT MARKED FOR USE IN PANEL SEE STICKER ON DEAD FRONT - NEC 110.3 2. INSTALL K.O SEALS IN JUNCTION BOXES FOR OLD WAREHOUSE LIGHTING 3. INSTALL MARKING PLATES FOR PANEL CL |