Permit: T07CM03011

Parcel: 115180050


Addresses:

1601 N ORACLE RD 06

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/07/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
1) PLUMBING FINAL OK
08/04/2008 PLUMBING - FINAL Not ready for Inspection 1. PROVIDE CLEAN BACTERIA REPORT
2. INSULATE ALL COLD WATER ABOVE CEILING AND ALL HOT WATER PIPING
3. REMOVE CHROME PLATED CLEANOUT COVER - MAKE CLEANOUT ACCESSIBLE - INSTALL COUNTER SUNK TAPPED CLEANOUT PLUG AND LEAVE COVER OFF FOR INSPECTION.
07/30/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. I INSTRUCTED YOU TO INSTALL AN AVB ON THE HOSE BIBBS
2. I ALSO TOLD YOU TO ADDRESS YOUR BUILDINGS PER PIMA COUNTY ADDRESSING REQUIREMENTS, WHICH YOU RECEIVED OVER 6 MONTHS AGO. I ALSO TOLD YOU I WOULD NOT ACCEPT CARDBOARD NUMBERS IN THE WINDOWS. I ALSO TOLD YOU CONTINUED "NOT READY" WOULD RESULT IN A REINSPECTION FEE. CONTRACTOR TO PAY REINSPECTION FEE.
07/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ADDRESS
07/24/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS
PRIOR TO CALLING FINAL.
THIS IS YOUR SECOND NOTIFICATION.
PLANS & PERMITS TO BE ON SITE AT ALL TIMES!
FAILURE TO DO SO WILL RESULT IN A REINSPECTION FEE
07/18/2008 PLUMBING - FINAL Partial Approval 1ST FLOOR CLOSET FLANGES OK. OK TO PLACE TOILETS.
07/17/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FAILURE TO COMPLY W/THE PREVIOUSLY NOTED REQUIREMENTS MAY RESULT IN REINSPECTION FEES
CALLED 977-0660 AS REQUESTED AND LEFT A MESSAGE W/VASQUEZ PLUMBING
04/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL 03036 FOR CLOSET FLANGES
OK TO COVER WALLS
12/31/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- POST YOUR BUILDING NUMBERS
- PLEASE CALL IN ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
- FIRST SIX UNITS FIRST FLOOR WEST SIDE OK TO COVER
- WATER TEST THROUGH ROOF OK