Permit: T07CM03011

Parcel: 115180050


Addresses:

1601 N ORACLE RD 06

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
EXIT LIGHTS TO BE ON CIRCUIT AREA SERVED 700.12 - BOTTOM PANEL
07/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOF

1. CURRENTLY LABEL PANELS
07/28/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH EXHAUST FAN
07/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. NM CABLE IN AIR DUCT
2. USE CORRECT SIZE CONDUCTOR FOR AMPACITY
3. PROPERLY GROUND JUNCTION BOX
07/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE A/C OUTLET BOX TO STRUCTURE
2. USE APPROVED EXTENDER RING AT RANGE OUTLETS AND PATCH DRYWALL - 314.20 & 21
ALSO, DEVICE AND SWITCHES
3. INSTALL AC UNITS
4. MISSING COVER PLATES
5. WATER DAMAGE WIRING AT SMOKE DETECTOR
07/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LABEL OUTSIDE COVERS MASTER PANELS
2. CHECK ROOF FOR MASTER EXHAUST FAN