Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/18/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED J-BOXES 2. HAVE J-BOX COVER MISSING 3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 4. DATA NOT COMPLETE 5. DEMO OLD LIGHT IN CEILING 6. LOW VOLTAGE WIRING NOT TO SECURE TO OTHER EQUIPMENT OR GRID SUPPORT WIRES - USE INDIVIDUAL SUPPORT. |