Permit: T07CM03009

Parcel: 10607030A


Addresses:

1351 W PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/08/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
10/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
VENT SIZE INCREASED ONE PIPE SIZE TO BE ALL THE WAY TO THE POINT OF VENT AT THE FIXTURE ADD HANGERS AS REQUIRED.
10/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS EXCEPT AT EXAM ROOM #1
2. 1 1/2" VENT MAY BE RUN A TOTAL OF 60'
ONLY 1/3 OF THAT LENGTH MAY BE HORIZONTAL (20') INCREASING VENT SIZE, ONE PIPE SIZE, NEGATES THIS REQUIREMENT OF THE CODE.
3. OK TO INSULATE ALL ABOVE GRADE WATER PIPING
09/30/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLAN CALLS FOR TYPE "L" COPPER
2. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4' BETWEEN HANGERS