Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER ALL AREAS |
|
| 10/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* VENT SIZE INCREASED ONE PIPE SIZE TO BE ALL THE WAY TO THE POINT OF VENT AT THE FIXTURE ADD HANGERS AS REQUIRED. |
|
| 10/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER WALLS EXCEPT AT EXAM ROOM #1 2. 1 1/2" VENT MAY BE RUN A TOTAL OF 60' ONLY 1/3 OF THAT LENGTH MAY BE HORIZONTAL (20') INCREASING VENT SIZE, ONE PIPE SIZE, NEGATES THIS REQUIREMENT OF THE CODE. 3. OK TO INSULATE ALL ABOVE GRADE WATER PIPING |
|
| 09/30/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLAN CALLS FOR TYPE "L" COPPER 2. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4' BETWEEN HANGERS |