Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH ALL LOW VOLTAGE AND DATA WIRING 2. HAVE OVERFILLED J-BOXES 3. ISOLATED GROUND NOT TO BE USED TO GROUND REGULAR EQUIPMENT 4. AIM EMERGENCY LIGHTS SO THEY ARE EFFECTIVE 5. PANEL DIRECTORIES TO BE CORRECTLY IDENTIFIED/NUMBER BREAKERS 6. INSTALL ALL BULBS 7. PANEL & MDS TO BE OPEN FOR INSPECTION 8. EMERGENCY LIGHTING TO BE PER NEC 700.12 PARTIAL INSPECTION ONLY ELECTRICIAN TO GO THROUGH THIS JOB TO MAKE SURE IT IS PER PLAN & CODE |