Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02998
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2007 | FRAMING | Approved | IVRS - Inspection :* | |
11/05/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL BLOCK SUPPORT FOR WATER HEATER LOOP 2) DRAFT STOP TUB AT 2ND FLOOR 3) ADD STUD IN PONY WALL AT TOP OF STAIRS 4) BLOCK REGISTERS 2ND FLOOR |
|
11/02/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MTT28B MISSING BY GARAGE SERVICE DOOR 2) 2 X 4 BLOCKING BETWEEN TOP CHORDS OF TOP HUNG FLOOR TRUSSES BETWEEN KITCHEN AND DINING AND LIVING ROOM PER 352 DETAIL 3) 2 X 6 HEADER MISSING TO 1/2 BATH BY STAIRS 4) SUPPORT 4 GANG BOX GOING UPSTAIRS 5) NAIL PROTECT WIRES THROUGHOUT WITHIN 1 1/4" 6) GROUND WIRES AT METAL BOXES 7) SUPPORT COLD LINE TO WATER HEATER 8) DRAFT STOP UNDER TUBS 9) INSULATE BEHIND MAIN FLOOR SHOWER 10) BLOCK REGISTERS 11) STOPPED INSPECTION-NOT READY |
|
11/01/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRADES STILL WORKING 2) FINISH STUCCO MESH |