Permit: T07CM02998

Parcel: 141350530

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02998

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2007 FRAMING Approved IVRS - Inspection :*
11/05/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL BLOCK SUPPORT FOR WATER HEATER LOOP
2) DRAFT STOP TUB AT 2ND FLOOR
3) ADD STUD IN PONY WALL AT TOP OF STAIRS
4) BLOCK REGISTERS 2ND FLOOR
11/02/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MTT28B MISSING BY GARAGE SERVICE DOOR
2) 2 X 4 BLOCKING BETWEEN TOP CHORDS OF TOP HUNG FLOOR TRUSSES BETWEEN KITCHEN AND DINING AND LIVING ROOM PER 352 DETAIL
3) 2 X 6 HEADER MISSING TO 1/2 BATH BY STAIRS
4) SUPPORT 4 GANG BOX GOING UPSTAIRS
5) NAIL PROTECT WIRES THROUGHOUT WITHIN 1 1/4"
6) GROUND WIRES AT METAL BOXES
7) SUPPORT COLD LINE TO WATER HEATER
8) DRAFT STOP UNDER TUBS
9) INSULATE BEHIND MAIN FLOOR SHOWER
10) BLOCK REGISTERS
11) STOPPED INSPECTION-NOT READY
11/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRADES STILL WORKING
2) FINISH STUCCO MESH