Permit: T07CM02983

Parcel: 128141190

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/20/2008 FRAMING Approved IVRS - Inspection :*
03/06/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1, 2 AND 5 FROM ABOVE
03/03/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDUIT FROM HOUSE TO SHOP AND ADDITION IS NOT DEEP ENOUGH. 18" PLASTIC-6" METAL
2) MESH OK ON SHOP, NOT READY ON HOUSE
3) REDO GAS TEST
4) NEED SMOKIES IN BED AND HALLWAY
5) NEED FHA STRAPS AT TOILET ABS
6) GROUT TUB HOLE