Permit: T07CM02982

Parcel: 12701003K

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/11/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
01/09/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
MANUFACTURE TESTING SHALL BE THIRD PARTY VERIFIED
PROVIDE THE LISTING FROM THE TESTING AGENCY
01/08/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- STEAM HUMIDIFIERS MAY POSE A HIGH RISK HAZARD OF CROSS CONTAMINATION AND REQUIRE A HIGH HAZARD BACKFLOW ASSEMBLY. SEE UPC TABLE 6-2 OR PROVIDE
3RD PARTY LISTING ADDRESSING POTABLE WATER CONNECTION FOR EQUIPMENT
10/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 10/3/07
10/03/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
HANGER ON 1/2 ABV. CEILING OK
WATER CONNECTION TO EQUIPMENT THAT MAY CONTAMINATE THE POTABLE SYSTEM SHALL BE PROTECTED W/AN APPROVED TYPE BACKFLOW PREVENTION ASSEMBLY. EQUIPMENT DOES NOT HAVE A USABLE AIR GAP.