Permit: T07CM02982

Parcel: 12701003K

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02982

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2008 ELECTRIC - FINAL Approved
04/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
AS BUILT REVISIONS NOT AS BUILT
03/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
*RECEIVED GENERATOR TEST REPORT
*ALL OTHER ITEMS COMPLETE

1. WAITING ON CORRECTED APPROVED AS BUILT PLANS
BOTH ENGINEER AND CITY STAMPS
03/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 3" EMT TO NEW DISCONNECT & 4-500 MCM
OK NEW 400 AMP DISCONNECT

1. FILL UNUSED OPENING IN PANEL COVER
2. SEPARATE GROUNDS & NEUTRALS 250.24
02/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUITS AT PANELS
2. CLEAN DIRT FROM BOTTOM OF PANELS
3. CHASE NIPPLES NOT APPROVED FITTINGS FOR LB -
4. NEED HANDLE TIE 605.7
5. FINISH 3, 4, 5, 6 AND 10 INSPECTION DATED 1/10/08
01/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEMS #3,4 AND 2 -- PHASE 1
5, 6, 8, 9 AND 10 -- PHASE 2
01/11/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK OFFICE FURNITURE CONNECTIONS
SOUTH END

1. FINISH PREVIOUS ITEMS
01/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH CONNECTIONS FOR OFFICE FURNITURE AND TIGHTEN LOOSE FITTINGS & LOCKNUTS & INSTALL ALL COVER PLATES
2. INSTALL AS PER 605.7
3. FINISH VDV ABOVE CEILING
4. PULL TV CORDS BELOW CEILING
5. FINISH UPS CONNECTIONS
6. FINISH UNDER FLOOR SERVER ROOM
7. NO GROUND FOR ISOLATED GROUND SYSTEM UPB
8. TIGHTEN PANEL LOCK NUTS
9. DERATE CONDUCTORS PER 310.15 AND INSTALL AS PER PLANS
10. BEAM CLAMP NOT LISTED FOR GROUNDING
11. LABEL PANELS AS PER 210.5(C)
12. USE CORRECT SIZED LUG FOR BONDING JUMPER
13. PANEL DIRECTORY TO BE AS PER 408.4
14. GROUNDING ELECTRODE CONDUCTOR TO BOND TO GROUNDED TERMINAL T-1

PARTIAL INSPECTION
01/10/2008 ELECTRIC - FINAL Not ready for Inspection 1. CONDUCTORS TO PANEL "WRAP" DERATE AND "TSA", "AC-1"
2. NO MORE THAN 360 DEG. IN A CONDUIT RUN
3. FINISH UPS #2 & CEC-3
4. PANEL MODIFIED (UPA) - BREAKER NOT LISTED FOR PANEL
5. EXISTING FEEDER UPA NOT AS PER PLANS
6. FINISH E MON METERS
7. FILL UNUSED OPENINGS TOP OF "EDS"
8. INSTALL 40A BREAKER "PPB"
9. BAKE A LITE LABELS
10. PANEL SCHEDULES AND ONE LINE DO NOT MATCH UP
11. FINISH PREVIOUS ITEM 1, 2, 4, 10, 12 & 14

RECEIVED CHECKS #27839 $150.00 AND 1347 $75.00 FOR INSPECTION