Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02982
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2008 | ELECTRIC - FINAL | Approved | ||
04/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* AS BUILT REVISIONS NOT AS BUILT |
|
03/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* *RECEIVED GENERATOR TEST REPORT *ALL OTHER ITEMS COMPLETE 1. WAITING ON CORRECTED APPROVED AS BUILT PLANS BOTH ENGINEER AND CITY STAMPS |
|
03/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 3" EMT TO NEW DISCONNECT & 4-500 MCM OK NEW 400 AMP DISCONNECT 1. FILL UNUSED OPENING IN PANEL COVER 2. SEPARATE GROUNDS & NEUTRALS 250.24 |
|
02/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUITS AT PANELS 2. CLEAN DIRT FROM BOTTOM OF PANELS 3. CHASE NIPPLES NOT APPROVED FITTINGS FOR LB - 4. NEED HANDLE TIE 605.7 5. FINISH 3, 4, 5, 6 AND 10 INSPECTION DATED 1/10/08 |
|
01/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #3,4 AND 2 -- PHASE 1 5, 6, 8, 9 AND 10 -- PHASE 2 |
|
01/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK OFFICE FURNITURE CONNECTIONS SOUTH END 1. FINISH PREVIOUS ITEMS |
|
01/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH CONNECTIONS FOR OFFICE FURNITURE AND TIGHTEN LOOSE FITTINGS & LOCKNUTS & INSTALL ALL COVER PLATES 2. INSTALL AS PER 605.7 3. FINISH VDV ABOVE CEILING 4. PULL TV CORDS BELOW CEILING 5. FINISH UPS CONNECTIONS 6. FINISH UNDER FLOOR SERVER ROOM 7. NO GROUND FOR ISOLATED GROUND SYSTEM UPB 8. TIGHTEN PANEL LOCK NUTS 9. DERATE CONDUCTORS PER 310.15 AND INSTALL AS PER PLANS 10. BEAM CLAMP NOT LISTED FOR GROUNDING 11. LABEL PANELS AS PER 210.5(C) 12. USE CORRECT SIZED LUG FOR BONDING JUMPER 13. PANEL DIRECTORY TO BE AS PER 408.4 14. GROUNDING ELECTRODE CONDUCTOR TO BOND TO GROUNDED TERMINAL T-1 PARTIAL INSPECTION |
|
01/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | 1. CONDUCTORS TO PANEL "WRAP" DERATE AND "TSA", "AC-1" 2. NO MORE THAN 360 DEG. IN A CONDUIT RUN 3. FINISH UPS #2 & CEC-3 4. PANEL MODIFIED (UPA) - BREAKER NOT LISTED FOR PANEL 5. EXISTING FEEDER UPA NOT AS PER PLANS 6. FINISH E MON METERS 7. FILL UNUSED OPENINGS TOP OF "EDS" 8. INSTALL 40A BREAKER "PPB" 9. BAKE A LITE LABELS 10. PANEL SCHEDULES AND ONE LINE DO NOT MATCH UP 11. FINISH PREVIOUS ITEM 1, 2, 4, 10, 12 & 14 RECEIVED CHECKS #27839 $150.00 AND 1347 $75.00 FOR INSPECTION |