Permit: T07CM02982

Parcel: 12701003K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/06/2008 ELECTRIC - ABOVE CEILING Approved
10/30/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK NORTH 1/2 OF 1ST FLOOR

1. FINISH VDV IN KITCHEN
10/29/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11
2. CABLES TO BE PLENIUM RATED

OK MC CABLES, CONDUIT & FIXTURES
10/22/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
FINISH PREVIOUS ITEMS
10/16/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK VDV CABLING SOUTH SIDE OF BUILDING
2. STILL NEED TO RESOLVE LAND ISSUE WITH T.V'S
10/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FINISH #3 OF PREVIOUS INSPECTIONS

OK TO TILE EXCEPT AS NOTED SOUTH HALF
10/03/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/12/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*