Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDER FLOOR EXCEPT AS NOTED 1. DEMOED ITEMS TO BE REMOVED 2. SEAL UNUSED RACEWAYS 3. CLEAN EXCESS TRASH FROM UNDER FLOOR 4. ABANDONED VDV CABLING TO BE AS PER 725.3 & 800.3 5. FINISH ELECTRIC ROOM AND SERVER ROOMS *WILL NEED TO SEE WORK STATION CONNECTIONS ALSO 605.7 WILL APPLY |
|
| 10/03/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. EXISTING MC CABLE AND FIXTURES DO NOT MEET CODE REQUIREMENT OF TIME OF INSTALLATION 2. VDV CABLING TO BE AS PER PREVIOUS INSPECTION 3. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 4. FINISH PREVIOUS INSPECTIONS |
|
| 09/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST FLOOR WALLS 1. SUPPORT MC CABLES AS PER 330.30 2. FIXTURES TO BE AS PER 410.16 3. VDV CABLING TO BE AS PER 725.3&6, 770.3&6, 800.3&6, 300.11 |
|
| 09/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT MC CABLE IN CHANNEL 2. SUPPORT FLEX CONDUIT OK ROOM 127 & 129 |