Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02968
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2008 | FRAMING | Approved | IVRS - Inspection :* | |
01/14/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHIM 2-2 X 6 HEADER ADDED FOR FIREPLACE FLUE 2) REGISTER BOX OVER L/R WINDOW BADLY TWISTED 3) RED HEADS COLUMNS BY STAIRS 4) WINDER TREADS MINIMUM DEPTH 6" 5) LIGHT IN FURNACE ROOM-E3803.4 6) INSTALL VACUUM BREAKER ON HOSE BIB 7) GAS PRESSURE TEST OK-COMPLETE PIPE TO FIREPLACE 8) SEVERAL DUCT BOOTS TWISTED OR DAMAGED |
|
01/07/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 16D NAILS NEEDED IN MTT AND LTT HOLDOWNS |