Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02964
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. USE APPROVED PARTS FOR GROUNDING TO STRUCTURAL 2. NEED BONDING SERVICE NIPPLE SEC 250.92 3. INSTALL MAIN BONDING JUMPER 4. NEED CABLE BRACING 5. LUG TOO LARGE FOR CONDUCTORS OK WALLS OFFICE, UTILITY, BATHROOM, & STORAGE |