02/09/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. USE APPROVED PARTS FOR GROUNDING TO STRUCTURAL
2. NEED BONDING SERVICE NIPPLE SEC 250.92
3. INSTALL MAIN BONDING JUMPER
4. NEED CABLE BRACING
5. LUG TOO LARGE FOR CONDUCTORS

OK WALLS OFFICE, UTILITY, BATHROOM, & STORAGE