Inspection History Details
Permit: T07CM02964
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. USE APPROVED PARTS FOR GROUNDING TO STRUCTURAL 2. NEED BONDING SERVICE NIPPLE SEC 250.92 3. INSTALL MAIN BONDING JUMPER 4. NEED CABLE BRACING 5. LUG TOO LARGE FOR CONDUCTORS OK WALLS OFFICE, UTILITY, BATHROOM, & STORAGE |