Permit: T07CM02962

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02962

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4 BOX TO SURFACE 314.20
2) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8
3) LABEL TIME CLOCK AND CONTACTOR
4) USE CORRECT SIZE WIRE SPLICES FOR NUMBER OF CONDUCTOR
5) LABEL PANEL DIRECTORY PER 408.4
6) BATH LIGHTS NOT PER PLANS
01/06/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CABLE BRACING AS PER MANUFACTURES REQUIREMENTS
2) A BOND FOR TEMP POWER FOR TEST MAYBE REQUIRED