Permit: T07CM02962
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4 BOX TO SURFACE 314.20 2) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8 3) LABEL TIME CLOCK AND CONTACTOR 4) USE CORRECT SIZE WIRE SPLICES FOR NUMBER OF CONDUCTOR 5) LABEL PANEL DIRECTORY PER 408.4 6) BATH LIGHTS NOT PER PLANS |
|
| 01/06/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CABLE BRACING AS PER MANUFACTURES REQUIREMENTS 2) A BOND FOR TEMP POWER FOR TEST MAYBE REQUIRED |