Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/08/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGE IN ROOM 207 OK |
|
| 04/07/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SECURE FLANGE TO FLOOR |
|
| 03/16/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1/2 HW & CW TO MS OK SECURE TRAP PRIMER |
|
| 03/05/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO SEE PIPING AT MOP SINK NEED TO SEE CLOSET FLANGES |
|
| 03/04/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 2. ABS IS TO BE LOCATED FROM METAL STUDS 3. WATER TEST ON ROOF DRAINS AND DWV OK 4. READ LETTER ALLOWING PEX 5. PIPING INCOMPLETE AT MOP SINK 6. REQUIRE 1" INSULATION ON 3/4" PEX AND LARGER |
|
| 11/25/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. HAVE GAS INSPECTIONS ADDED TO PERMIT 2. PROVIDE APPROVED REVISIONS 3. PROVIDE WELDER CERTS 4. CORRECT ANY MISSING PIPE SUPPORTS 5. RECALL FOR INSP. BOTH PLUMBING AND MECHANICAL 6. 100 PSI TEST ON WELD PIPE 7. 14 PSI ON LOW PSI SYSTEM |