Permit: T07CM02941

Parcel: 114600800

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
03/21/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
03/19/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/20/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. INSTALL SERVICE CONDUCTORS FROM SES TO TEP XFMR
2. BOND WATER PIPE
3. GROUND RODS TO BE MIN. 6' APART
4. PLAN DOES NOT INDICATE SERVICE CONDUCTOR SIZE
5. OK 2 - 4" PVC FROM SES TO EXISTING 4" PVC. INSTALL WARNING RIBBON PER NEC 300.5
6. INTERIOR OF UNIT ALL TRIMMED OUT
7. NOT A COMPLETE SERVICE INSPECTION RECALL WHEN READY