Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/28/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAULK ALL PENETRATIONS 2) BANG PLATE CONDENSATE LINE KITCHEN SIDE 3) NEED POTABLE H20 TEST AND DWV SYSTEM H20 TEST 4) SECURE LINE SET, FOR A/C AT GARAGE WALL 5) DRY DUCT NOT INSIDE WALL LINE 6) BACK NAIL HIP TRUSS FRONT BEDROOM 7) TUB-SURROUND BACKING VERT SIDES 8) SECURE PEX AT BATHROOM PLUMB WALL AND KIT 9) SHOWER DIVERTER WALL NOT SECURED 10) BANG PLATE KIT SINK TRAP ARM AND VENT 11) INSTALL A35 AT KIT SHEAR, TO TRUSS 12) LOOSE B/PLATE LIV TO HALL AND OPENING 13) NEED A HEADER AT BATHROOM WINDOW |
|
| 01/30/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FRONT LID OK TO ROCK ABOVE FOYER |