Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/03/2008 FRAMING Approved IVRS - Inspection :*
03/28/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CAULK ALL PENETRATIONS
2) BANG PLATE CONDENSATE LINE KITCHEN SIDE
3) NEED POTABLE H20 TEST AND DWV SYSTEM H20 TEST
4) SECURE LINE SET, FOR A/C AT GARAGE WALL
5) DRY DUCT NOT INSIDE WALL LINE
6) BACK NAIL HIP TRUSS FRONT BEDROOM
7) TUB-SURROUND BACKING VERT SIDES
8) SECURE PEX AT BATHROOM PLUMB WALL AND KIT
9) SHOWER DIVERTER WALL NOT SECURED
10) BANG PLATE KIT SINK TRAP ARM AND VENT
11) INSTALL A35 AT KIT SHEAR, TO TRUSS
12) LOOSE B/PLATE LIV TO HALL AND OPENING
13) NEED A HEADER AT BATHROOM WINDOW
01/30/2008 FRAMING Partial Approval IVRS - Inspection :*
1) FRONT LID OK TO ROCK ABOVE FOYER