Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT ELECTRIC JUNCTION BOX OTHER THAN GRID 2) EXPOSED CONDUCTORS-CANOPY TO BE ATTACHED TO AN ELECTRICAL BOX 3) FIXTURES TO BE ATTACHED TO GRID 410.16 4) EM LIGHTING TO BE AS PER 700.12 5) SUPPORT CONDUIT ABOVE PANEL 6) MISSING OUTLET COVERS 7) INSTALL LIGHTING IN ROOMS 8) SUPPORT VDV CABELING 725.6 PREVIOUS INSPECTION |