Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MUST MAINTAIN 36" OF CLEAR SPACE IN FRONT OF PANELS AND SERVICE EQUIP. -- 110.26 NEC 2. SERVICE NOT GROUNDED PER CODE. INSTALL (2) GROUND RODS, 6' MIN. APART & GROUND SERVICE DISCONNECT PER ART. 250 NEC 3. LIGHT ON WALL IN CLOSET NEEDS TO BE RESECURED TO BOX 4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE & LABEL OTHER EQUIP AS TO IDENTIFY USE AND OR SPACE #'S |