Permit: T07CM02894

Parcel: 124062110

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02894

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MUST MAINTAIN 36" OF CLEAR SPACE IN FRONT OF PANELS AND SERVICE EQUIP. -- 110.26 NEC
2. SERVICE NOT GROUNDED PER CODE. INSTALL (2) GROUND RODS, 6' MIN. APART & GROUND SERVICE DISCONNECT
PER ART. 250 NEC
3. LIGHT ON WALL IN CLOSET NEEDS TO BE RESECURED TO BOX
4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE & LABEL OTHER EQUIP AS TO IDENTIFY USE AND OR SPACE #'S