Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/06/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - BALANCE REPORT NOT ON SITE - G.C STATES THERE WERE NOT ISSUES WITH OUTSIDE AIR PARAMETERS - ROOF LADDER STILL NOT INSTALLED - NO LIFE SAFETY ISSUES BEYOND LADDER PENDING, SEE BUILDING INSPECTOR FOR TEMP C OF O |
|
| 10/31/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/22/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PER IMC 306.5 PROVIDE ROOF LADDER AT LOCATION ABOVE 30" 2. PROVIDE CONDENSATE TRAPS PER PLAN DETAIL 3. IDENTIFY UNIT DATA PLATE 4. PROVIDE ACCESS TO FILTER RACK 5. PROVIDE AIR BALANCE REPORT 6. TEST DUCT SMOKE DETECTORS |