Permit: T07CM02890

Parcel: 11604120A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/19/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/06/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- BALANCE REPORT NOT ON SITE
- G.C STATES THERE WERE NOT ISSUES WITH OUTSIDE AIR PARAMETERS
- ROOF LADDER STILL NOT INSTALLED
- NO LIFE SAFETY ISSUES BEYOND LADDER PENDING, SEE BUILDING INSPECTOR FOR TEMP C OF O
10/31/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/22/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PER IMC 306.5 PROVIDE ROOF LADDER AT
LOCATION ABOVE 30"
2. PROVIDE CONDENSATE TRAPS PER PLAN DETAIL
3. IDENTIFY UNIT DATA PLATE
4. PROVIDE ACCESS TO FILTER RACK
5. PROVIDE AIR BALANCE REPORT
6. TEST DUCT SMOKE DETECTORS