Permit: T07CM02890

Parcel: 11604120A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/10/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. INSTALL AVB ON HOSE BIB TODAY!
2. RESTROOM #102 NOT ON ALT. #1
3. SHOWER DRAINS SEEM OK
4. WATER HEATER REVISED TO ELECTRIC
OK TO INSULATE HOT & TEMPERED WATER
5. OK TO COVER ALL AREAS
08/12/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WILL NEED TO RECHECK RESTROOM #102 AFTER THE
TILE IS SET
2. WILL NEED TO SEE SHOWER RECEPTORS INSTALLED
AND TESTED
3. ALL OTHER FLANGES ON STAINED AND SEALED CONCRETE FLOORS OK
07/02/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WORK PERFORMED, NOT DESIGNATED ON THE PLAN, REQUIRES SEPARATE PERMITS.
06/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ADD TWO HANGERS AS REQUIRED
OK TO COVER WALLS
2. NEED TO SEE FLANGES
05/28/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS AT CLASSROOM BLDG.
OK TO INSULATE HOT PIPING