Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* BOND POLES JUNCTION BOXES |
|
| 10/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* *A REFEE MAY BE ASSESSED IF INSPECTIONS ARE NOT READY PER ADMIN. CODES 1. CIRCUIT DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS DISTINGUISHABLE FROM ONE ANOTHER 2. LABEL CONTACTOR AND TIME CLOCK 3. USE TERMINAL END WITH STRANDED CONDUCTORS AT SCREEN TERMINALS 4. EXIT LIGHT & EM LIGHTS NOT WORKING INSIDE & OUTSIDE 5. EXIT LIGHT TO BE AS PER 700.12(P) 6. FINISH PREVIOUS ITEMS |
|
| 10/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PULL BOX LOCATION IN MIDDLE OF RUN OF POOL 2. SPLICES TO BE FOR WET LOCATION 3. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 408.6 4. CONDUCTOR COLORS TO BE AS PER CITY AMENDMENT 5. BOND POLE AT HAND HOLD 6. FILL UNUSED OPENING AT PANEL 7. SEPARATE GROUNDS & NEUTRALS AT OLD DISCONNECT 8. STRAP CONDUIT BY SES PER CODE 9. TIGHTEN CONDUCTORS UNDER TERMINAL SCREWS ON DEVICES 10. BOXES MORE THAN 1/4" -- 314.20 ROOF: 1. ONLY ONE CONDUCTOR PER LUG TERMINATION 2. TIGHTEN CONDUCTOR TERMINATIONS 3. DISCONNECT DOOR TO OPEN 90 DEG. |