Permit: T07CM02890

Parcel: 11604120A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
BOND POLES JUNCTION BOXES
10/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*A REFEE MAY BE ASSESSED IF INSPECTIONS ARE NOT READY PER ADMIN. CODES

1. CIRCUIT DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS DISTINGUISHABLE FROM ONE ANOTHER
2. LABEL CONTACTOR AND TIME CLOCK
3. USE TERMINAL END WITH STRANDED CONDUCTORS AT SCREEN TERMINALS
4. EXIT LIGHT & EM LIGHTS NOT WORKING INSIDE & OUTSIDE
5. EXIT LIGHT TO BE AS PER 700.12(P)
6. FINISH PREVIOUS ITEMS
10/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PULL BOX LOCATION IN MIDDLE OF RUN OF POOL
2. SPLICES TO BE FOR WET LOCATION
3. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 408.6
4. CONDUCTOR COLORS TO BE AS PER CITY AMENDMENT
5. BOND POLE AT HAND HOLD
6. FILL UNUSED OPENING AT PANEL
7. SEPARATE GROUNDS & NEUTRALS AT OLD DISCONNECT
8. STRAP CONDUIT BY SES PER CODE
9. TIGHTEN CONDUCTORS UNDER TERMINAL SCREWS ON DEVICES
10. BOXES MORE THAN 1/4" -- 314.20

ROOF:
1. ONLY ONE CONDUCTOR PER LUG TERMINATION
2. TIGHTEN CONDUCTOR TERMINATIONS
3. DISCONNECT DOOR TO OPEN 90 DEG.