Permit: T07CM02877

Parcel: 122030220

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/25/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
10/24/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS STILL HAVE NOT BEEN MADE
PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTIN
REMOVE INSULATION AROUND WATER HEATER VENT PIPES
10/18/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- ISN'T IT OBVIOUS THAT THE KINKED FLEX NEEDS A HANGER STRAP?
- AND ISN'T IT OBVIOUS THAT THE EXHAUST OUTLET WAS DESIGNED TO TAKE A 1/2" LONG SCREW IN THE BOTTOM WITHOUT INTERFERING WITH THE BACKDRAFT DAMPER?
- WHERE ARE THE CONDENSATE DRAINS
10/17/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- UNIT 1 FLEX DUCT TO BEDROOM KINKED ABOVE GAS LINE
- SCREW EXHAUST DUCTS TO OUTLETS ON FANS
- PROVIDE CONDENSATE DRAIN LINES

NOTE TO MECHANICAL CONTRACTOR: DO NOT USE 1/2" DUCT LINER FOR ANYTHING. THE R VALUE IS NOT ADEQUATE AT R2 MIN. REQUIREMENT IS R 4.2