Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
| 10/24/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS STILL HAVE NOT BEEN MADE PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTIN REMOVE INSULATION AROUND WATER HEATER VENT PIPES |
|
| 10/18/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - ISN'T IT OBVIOUS THAT THE KINKED FLEX NEEDS A HANGER STRAP? - AND ISN'T IT OBVIOUS THAT THE EXHAUST OUTLET WAS DESIGNED TO TAKE A 1/2" LONG SCREW IN THE BOTTOM WITHOUT INTERFERING WITH THE BACKDRAFT DAMPER? - WHERE ARE THE CONDENSATE DRAINS |
|
| 10/17/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - UNIT 1 FLEX DUCT TO BEDROOM KINKED ABOVE GAS LINE - SCREW EXHAUST DUCTS TO OUTLETS ON FANS - PROVIDE CONDENSATE DRAIN LINES NOTE TO MECHANICAL CONTRACTOR: DO NOT USE 1/2" DUCT LINER FOR ANYTHING. THE R VALUE IS NOT ADEQUATE AT R2 MIN. REQUIREMENT IS R 4.2 |