Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION 1. BREAKERS TO BE LISTED BY MANUFACTURES |
|
| 06/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED ILLUMINATION AT PANELS & SES 110.26 2. MAINTAIN DEDICATED SPACE ABOVE PANELS - 110.26 3. NEW FEEDERS TO BE AS PER 408.3 *LAUNDRY ROOM MAINTAIN WORKING CLEARANCE AT DISCONNECT FOR PUMP AS DISCUSSED |
|
| 05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL SCHED. TO BE LEGIBLE - NO ABBREVIATIONS 2. PANEL COVER CANNOT BE OPENED 3. PROTECT CONDUCTORS AND CABLES FROM SHARP METAL EDGES 4. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM PANEL 5. FILL UNUSED OPENINGS 6. USE CORRECT BREAKERS FOR NM AMPACITY 330.26 7. FIXTURES TO MOUNT TO BOXES ON WALLS WITHOUT GAPS 8. GROUND FIXTURE HARDWARE/PLATES 9. NEED AN ADAPTOR TO CHECK ARC FAULTS |