Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IF MC IS TO BE BUNDLED MORE THAN 24", CONDUCTORS MUST BE DERATED FOR AMPACITY - NEC 310.15 B2 2. WIRING NOT PER PLAN, CONDUCTOR SIZES FOR TRANSFORMER TO BE PER PLAN, FUSE SIZE ETC. TRANSFORMER TO HAVE PROPERLY SIZED FEEDER & OVERCURRENT PROTECTION 3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING CONNECTIONS 4. MAKE SURE PREVIOUS CORRECTIONS COMPLETE NEED TO PAY REINSPECTION FEE |
|
| 11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING WEST SIDE EXIT SIGN 2. MISSING GROUND BAR, SEE NOTE (4) 3. MISSING RECEPTACLES, SEE NOTE (5) 4. RACK FRAME TO BE GROUNDED PARTIAL INSPECTION WIRING TO BE PER PLAN, NEED TO GO THROUGH INSTALLATION, HAVE EQUIPMENT OPEN |