Permit: T07CM02854

Parcel: 13734001A


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02854

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS, CALL FOR ABOVE CEILINGS AFTER LIGHTS HUNG
08/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- MC CABLE MUST BE 1 1/4" MIN. FROM FACE OF STUD WHEN INSTALLED FROM INSIDE OF STUD TRACK VERTICAL
- SUPPORT EMT WITHIN 3' OF TERM PER CODE