Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02854
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS, CALL FOR ABOVE CEILINGS AFTER LIGHTS HUNG |
|
08/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - MC CABLE MUST BE 1 1/4" MIN. FROM FACE OF STUD WHEN INSTALLED FROM INSIDE OF STUD TRACK VERTICAL - SUPPORT EMT WITHIN 3' OF TERM PER CODE |