Permit: T07CM02837

Parcel: 10408075N


Addresses:

4491 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. IDENTIFY ALL RTU'S
2. IDENTIFY PHASE CONDUCTORS
3. STRAP FLEX WITHIN 12" OF ENCLOSURES

INSIDE
1. PROVIDE GROUND FOR TELCO PER PLAN/GROUND RACK
2. EMERGENCY CANNOT WORKING IN HALL
3. CHECK PANEL DIRECTORY
4. HAVE SEVERAL LOOSE RECEPTACLES, ALSO RECEPTACLES NOT TO SIT BACK OF PLATE
5. CLOSE UP ALL BOXES, INSTALL ALL COVER PLATES