Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) RECEIVED LETTER FROM ENGINEER FOR SERVICE REVISION |
|
| 12/31/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY GROUNDING, UFER & TWO SERVICES TIE 2. PROVIDE LETTER FROM ENGINEER OF RECORD ADDRESSING CHANGES TO FIELD INSTALLATION 3. INSTALL COMPLETE RACEWAY FROM TRANSFER SWITCH TO GEN. CONTROL CABINET |
|
| 12/28/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW 150KVA GENERATOR WITH A 400 AMP MAIN BREAKER 2. IDENTIFY SERVICE DISCONNECT AS SUCH 3. PLANS SHOW A CT CAN FOR SERVICE CONDUCTORS 4. RACEWAY FOR GENERATOR FEEDER TO BE COMPLETE FROM SLAB TO J-BOX FOR TERMINATION 5. BOND ALL INTERIOR METAL PIPING TO SERVICE DISCONNECT ENCLOSURE PARTIAL INSPECTION - DAN S. TO CONTINUE |
|
| 12/27/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) NEED THE APPROVED PLAN ON SITE FOR INSPECTION 2) NO INSPECTION AT THIS TIME |