Permit: T07CM02830

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/03/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) RECEIVED LETTER FROM ENGINEER FOR SERVICE REVISION
12/31/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY GROUNDING, UFER & TWO SERVICES TIE
2. PROVIDE LETTER FROM ENGINEER OF RECORD ADDRESSING CHANGES TO FIELD INSTALLATION
3. INSTALL COMPLETE RACEWAY FROM TRANSFER SWITCH TO GEN. CONTROL CABINET
12/28/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS SHOW 150KVA GENERATOR WITH A 400 AMP MAIN BREAKER
2. IDENTIFY SERVICE DISCONNECT AS SUCH
3. PLANS SHOW A CT CAN FOR SERVICE CONDUCTORS
4. RACEWAY FOR GENERATOR FEEDER TO BE COMPLETE FROM SLAB TO J-BOX FOR TERMINATION
5. BOND ALL INTERIOR METAL PIPING TO SERVICE DISCONNECT ENCLOSURE

PARTIAL INSPECTION - DAN S. TO CONTINUE
12/27/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1) NEED THE APPROVED PLAN ON SITE FOR INSPECTION
2) NO INSPECTION AT THIS TIME