Permit: T07CM02829

Parcel: 13003022B


Addresses:

2712 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/12/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/07/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/03/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/02/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- NEED TO SEE WELDS ON GREASE DUCTS PRIOR TO FIRE WRAP -- 506.3.3.6 2006 IMC
- 2 LAYERS OF FIRE WRAP REQUIRED 506.3.10 #1
- AUTOMATIC ACTIVATION OF EXHAUST FAN 507.2.1.1
- NO COMBUSTIBLE MATERIAL WITHIN 18" OF HOOD 507.9
- PROPERLY SEAL VAPOR BARRIERS. SEE DETAILS.