Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/07/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/03/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/02/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - NEED TO SEE WELDS ON GREASE DUCTS PRIOR TO FIRE WRAP -- 506.3.3.6 2006 IMC - 2 LAYERS OF FIRE WRAP REQUIRED 506.3.10 #1 - AUTOMATIC ACTIVATION OF EXHAUST FAN 507.2.1.1 - NO COMBUSTIBLE MATERIAL WITHIN 18" OF HOOD 507.9 - PROPERLY SEAL VAPOR BARRIERS. SEE DETAILS. |