Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM02829

Parcel: 13003022B


Addresses:

2712 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSTALL IN USE COVERS FOR OUTDOOR RECEPTS EXPOSED TO RAIN - EM LIGHTING TO BE ON AREA SERVED CIRCUITS PER 700 NEC - KITCHEN 110V OUTLETS (RECEPTS) TO BE GFI PROTECTED PER NEC 210