Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2008 | ELECTRIC - UNDERGROUND | Approved | ||
| 06/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK U.G CONDUITS FOR MCC's AND X-FORMERS OUTSIDE BLD. VERIFY WORKING CLEARANCES FOR EQUIP. BEFORE INSTALLING |
|
| 05/23/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3 - 4" CONDUITS FOR SECONDARY POWER & PHONE/DATA BLD. TO POLE & X-FORMER |
|
| 05/05/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 3 - 4" PVC FROM CT CABINET HEADING SOUTH 10' 2. OK 2 - 4" PVC FROM CT CABINET TO SES LOCATION 3. PROVIDE REVISION FOR CHANGE IN SERVICE CONDUCTOR SIZING 4. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTOR RACEWAYS PER NEC 300.5 |