Permit: T07CM02823

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/08/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/10/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- DWV W/TEST THRU ROOF OK TO COVER
- WATER PIPING W/TEST INSTALLED PER PLAN
- MIN. REQUIREMENT FOR ENERGY EFFICIENCY IS 8' OF INSULATION TO AND FROM WH
- POTABLE WATER OUTLETS W/HOSE ATTACHMENTS SHALL BE PROTECTED AGAINST BACKFLOW CONDITIONS WITH THE APPROPRIATE TYPE OF ASSEMBLY OR DEVICE PER
UPC SEC 603.4.7
01/09/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/08/2008 PLUMBING - INTERMEDIATE Cancelled CANCELLED PER GLENN
11/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RP CERT RECEIVED FOR 009 AT FISH EQUIPMENT
OK TO USE WATER
11/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV AT FS1 AND SS1 W/TEST THRU ROOF OK
RP NOT PER SPEC
RP REQUIRES CERTIFICATION PRIOR TO USE