Permit: T07CM02823

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/15/2008 ELECTRIC - INTERMEDIATE Partial Approval BOND NIPPLES PER 250.92 AND SIZE PER 250.102 AND 250.66
RECEIVED MONEY ORDER #57817921106 FOR $150.00
01/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
01/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH OF MATCH LINE WALL
01/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
A MEETING WAS HELD AT TEN AM (10:00 AM) TO DISCUSS SITUATION WITH INSTALLED SWITCHGEAR.
PRESENT WERE:
STEVE RITTER & GLENN WELLS FROM MCDAVID CONST.
STEVE SCHUMACHER FROM BROWN WHOLESALE ELECTRIC
STEVE RUSSELL & DENNIS BALL FROM LARSON BAKER,
MIKE FORD FROM PETSMART AND RICK HOLLANDER (CITY OF TUCSON ELECTRICAL INSPECTOR)

CODE VIOLATION AND LIGHT SAFETY CONCERNS WERE DISCUSSED - MCDAVID CONST. WILL CONSULT WITH AN ENGINEER AS TO DESIGN AND DIRECTION WITH TO PROCEED SPECIAL INSPECTIONS WILL BE AVAILABLE AT $150.00 FOR 2HR CALL-OUT AND $75.00 PER HOUR AFTERWARDS IF NEEDED. PLANS CAN BE ADDED AS A REVISION PER BETH GRANT.
01/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM 200
12/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NEED TO CHECK ON SERVICE INSPECTIONS FROM PREVIOUS YEARS FOR INSPECTIONS
11/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY LISTING ? SYSTEM BEFORE USAGE
2) OK JUNCTION BOXES AT TANKS
11/09/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
11/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLEASE HAVE WILDAN ADD 02010 TO PERMIT
2. SEAT PVC & CONDUIT FITTINGS CORRECTLY & VERIFY NO MORE THAN 360 DEG. IN RUN
3. DO NOT ENERGIZE PANEL UNTIL CLEARED FOR USE
4. VERIFY LISTING & LABELING FOR FILTRATION EQUIPMENT ASSEMBLY - 110.3

* DO NOT OCCUPY AREAS WITHOUT PARTIAL FINALS TO CLEAR AREAS FOR USAGE.