Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED (4) BACKFLOW CERTIFICATIONS & CLEAN BACTERIA |
|
| 01/07/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MENS RESTROOM FLUSH HANDLE TO BE TO WIDE SIDE OF ROOM FOR STOOL 2. COMPLETE INSTALL OF ALL APPLIANCES WITH CORRECT BACKFLOW PROTECTION & CERTIFICATIONS 3. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION ON DISHWASHER DRAINAGE 4. PROVIDE CORRECT CLEANOUT FOR 2-COMP OF 3-COMP SINK 5. ALL INDIRECT DRAINAGE TO HAVE 1" AIR GAP AT TERMINATION 6. PROVIDE DOMES & GRATES FOR FLOOR SINKS 7. PROVIDE 8' IN & 8' OUT INSULATION ON HOT & COLD PIPING OF WATER HEATER 8. MAKE MOP SINK WATER TIGHT AT FLOOR & WALL 9. PROVIDE CORRECT RATED BTU FLEXES AT ROOFTOP UNITS 10. GREASE TRAP TO BE FLUSH WITH PAVEMENT TO PREVENT TRIPPING HAZARD 11. PROVIDE CLEAN BACTERIA REPORT FOR POTABLE WATER SYSTEM |