Permit: T07CM02816

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM02816

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED (4) BACKFLOW CERTIFICATIONS & CLEAN BACTERIA
01/07/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. MENS RESTROOM FLUSH HANDLE TO BE TO WIDE SIDE OF ROOM FOR STOOL
2. COMPLETE INSTALL OF ALL APPLIANCES WITH CORRECT BACKFLOW PROTECTION & CERTIFICATIONS
3. PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION ON DISHWASHER DRAINAGE
4. PROVIDE CORRECT CLEANOUT FOR 2-COMP OF 3-COMP SINK
5. ALL INDIRECT DRAINAGE TO HAVE 1" AIR GAP AT TERMINATION
6. PROVIDE DOMES & GRATES FOR FLOOR SINKS
7. PROVIDE 8' IN & 8' OUT INSULATION ON HOT & COLD PIPING OF WATER HEATER
8. MAKE MOP SINK WATER TIGHT AT FLOOR & WALL
9. PROVIDE CORRECT RATED BTU FLEXES AT ROOFTOP UNITS
10. GREASE TRAP TO BE FLUSH WITH PAVEMENT TO PREVENT TRIPPING HAZARD
11. PROVIDE CLEAN BACTERIA REPORT FOR POTABLE WATER SYSTEM