Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* WATER TEST GREASE TRAP OK |
|
| 10/08/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT UNDERGROUND SANITARY & GREASE WASTE PER REDLINE ON SITE OK 1. SHALL SEE TEST ON GREASE TRAP AND PIPE WRAPS PRIOR TO CONCRETE |
|
| 10/03/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. TEST TO BE IN PLACE AT TIME OF INSPECTION 2. PROVIDE MINIMUM 1/4" PER FOOT FALL ON ALL PIPING 3. PROVIDE CORRECT DRAINAGE FITTINGS 4. PROVIDE CORRECT UPPER TERMINAL CLEANOUTS 5. PROVIDE REDLINE ON SITE FOR CHANGES 6. POST SUITE# ON THIS SITE |