Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02816
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/02/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE ACCESS TO SWITCH GEAR. NEEDS TO BE UNLOCKED AND OPENED 2. PANEL BOARD NOT LISTED FOR USE WITH SPLIT BREAKERS 3. VERIFY RECEPTACLES UNDER TYPE 1 HOOD ARE WIRED TO SHUT OFF WHEN ANSUL SYSTEM ACTIVATES 4. VERIFY GAS & WATER BONDING 5. CANNOT SUPPORT MC CABLE TO SPRINKLER PIPING 6. LIGHT FIXTURES TO BE SECURED TO GRID 7. HAVE ENGINEER PROVIDE DRAWING TO ANSUL INTERIOR SYSTEM 8. RECALL WHEN READY |
|
12/21/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING FRONT OF RESTAURANT DINING AREA 2) RECALL FOR KITCHEN AREA |