Permit: T07CM02816

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM02816

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/02/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ACCESS TO SWITCH GEAR. NEEDS TO BE UNLOCKED AND OPENED
2. PANEL BOARD NOT LISTED FOR USE WITH SPLIT BREAKERS
3. VERIFY RECEPTACLES UNDER TYPE 1 HOOD ARE WIRED TO SHUT OFF WHEN ANSUL SYSTEM ACTIVATES
4. VERIFY GAS & WATER BONDING
5. CANNOT SUPPORT MC CABLE TO SPRINKLER PIPING
6. LIGHT FIXTURES TO BE SECURED TO GRID
7. HAVE ENGINEER PROVIDE DRAWING TO ANSUL INTERIOR SYSTEM
8. RECALL WHEN READY
12/21/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILING FRONT OF RESTAURANT DINING AREA
2) RECALL FOR KITCHEN AREA