Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T07CM02814
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* SEWER OK WATER PIPING COPPER TO PVC CONNECTION OK AT EXTERIOR CONTRACTOR WILL PROVIDE BLUE TRACER WIRE PRIOR TO COVERING PVC |
|
07/30/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* - DRAIN PIPING INSIDE BUILDING OK TO COVER - SEWER PIPING FROM 2-WAY CO TO CONNECTION W/EXISTING DENIED. - REMOVE ROCKS, PROVIDE UNIFORM SLOPE AT MIN. 2% AND SUPPORT PIPING W/CLEAN COMPACTABLE DIRT - PVC WATER PIPING MAY NOT ENTER BUILDING |
|
07/27/2007 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EACH FIXTURE REQUIRES A VENT PLAN REQUIRES 3" CO ON SINK RISER BUILDING SEWER REQUIRES CO TRACER WIRE REQUIRED ON EXTERIOR PIPING |