Permit: T07CM02814

Parcel: 11105245C


Addresses:

3063 N ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02814

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AT PANEL - USE PROPER BREAKER BLANK COVERS, NUMBER ALL BREAKERS (NEAT, LEGIBLE)
2. RECEPTACLES - NEED BOX EXTENDER WHERE REC. IS SET BACK IN WALLS, THEY ARE TO BE FLUSH OR EXTEND FROM COVER AND NOT LOOSE, REPLACE CRACKED COVERS.
3. HOT WATER HEATER TO HAVE PROPER FRONT WORKING CLEARANCE, STRAP FLEX
4. MAX DISHWASHER CORD LENGTH 48"
5. STRAP EXTERIOR EMT
6. PROPERLY SUPPORT/SECURE MC ABOVE CEILING
08/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
2. HAVE DEAD RECEPTACLE N.W OFFICE
3. HAVE SEVERAL LOOSE RECEPTACLES
4. HAVE OPEN J-BOXES
5. STRAP EXTERIOR EMT
6. INSTALL ALL DEVICE COVER SCREWS
7. ALARM (FIRE) NOT FUNCTIONING PROPERLY
8. DISHWASHER NOT INSTALLED
9. WIRING NOT PER PLAN

PROVIDE WATER HEATER INSTALL INSTRUCTIONS
AND LADDER FOR ROOF INSPECTION

10. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING