Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02814
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AT PANEL - USE PROPER BREAKER BLANK COVERS, NUMBER ALL BREAKERS (NEAT, LEGIBLE) 2. RECEPTACLES - NEED BOX EXTENDER WHERE REC. IS SET BACK IN WALLS, THEY ARE TO BE FLUSH OR EXTEND FROM COVER AND NOT LOOSE, REPLACE CRACKED COVERS. 3. HOT WATER HEATER TO HAVE PROPER FRONT WORKING CLEARANCE, STRAP FLEX 4. MAX DISHWASHER CORD LENGTH 48" 5. STRAP EXTERIOR EMT 6. PROPERLY SUPPORT/SECURE MC ABOVE CEILING |
|
08/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 2. HAVE DEAD RECEPTACLE N.W OFFICE 3. HAVE SEVERAL LOOSE RECEPTACLES 4. HAVE OPEN J-BOXES 5. STRAP EXTERIOR EMT 6. INSTALL ALL DEVICE COVER SCREWS 7. ALARM (FIRE) NOT FUNCTIONING PROPERLY 8. DISHWASHER NOT INSTALLED 9. WIRING NOT PER PLAN PROVIDE WATER HEATER INSTALL INSTRUCTIONS AND LADDER FOR ROOF INSPECTION 10. ROMEX NOT ALLOWED ABOVE SUSPENDED CEILING |