Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM02790

Parcel: 125076370

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM02790

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/17/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- INSTALL 45 DEG. BRANCH TAPS PER M2.4-2
- FSK TAPE ALL DUCT WRAP EXPOSED INSULATION TO ENSURE SEALED VAPOR BARRIER.
- PROVIDE 2ED DRAIN PAN PER DETAIL M2.4(6)
- ALL CONDENSATE DRAIN LINES TO BE MINIMUM 3/4" I.D