Permit: T07CM02790

Parcel: 125076370

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02790

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED PROPER HEAT STRIPS
2. RE-IDENTIFY RTU-4 DATA LABEL
12/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
HEAT STRIPS FOR AIR HANDLERS
TO BE ONLY THOSE LISTED FOR USE IN HANDLERS PER APPROVED ACCESSORY LABEL ON UNIT - WARREN STRIPS NOT APPROVED - NEC 110.3B