Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02790
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/30/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING TILES EXCEPT AROUND AIR HANDLERS AND DISCONNECTS 2) REMOVE TEMP CEILING POWER |
|
11/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. VDV CABELING TO BE INDEPENDENTLY SUPPORTED - NOT LAYING ON PIPES OR DUCTS - SUPPORT WIRES TO BE AS PER 300.11 2. M/C CABLE TO BE SUPPORTED AT 6' INTERVALS 3. MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS 4. NO MORE THAN 360 DEG. IN A CONDUIT RUN 5. BOND CONTACTOR ENCLOSURE 6. LABEL CONTACTOR & TIME CLOCK 7. MEDIA CENTERS - FILL UNUSED OPENINGS & PROTECT CABLES ENTERING CENTERS. |
|
11/27/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) ALL CEILING TILES TO BE REMOVED FOR CEILING INSPECTION EXCEPT THOSE TILES NEEDED TIO MOUNT EQUIPMENT |
|
10/26/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER HARD LIDS/SOFFITS NOTE: J-BOXES HAVE OFFICE AREA STILL TO BE COMPLETED |