Permit: T07CM02790

Parcel: 125076370

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM02790

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/30/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILING TILES EXCEPT AROUND AIR HANDLERS AND DISCONNECTS
2) REMOVE TEMP CEILING POWER
11/29/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. VDV CABELING TO BE INDEPENDENTLY SUPPORTED -
NOT LAYING ON PIPES OR DUCTS - SUPPORT WIRES TO BE
AS PER 300.11
2. M/C CABLE TO BE SUPPORTED AT 6' INTERVALS
3. MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS
4. NO MORE THAN 360 DEG. IN A CONDUIT RUN
5. BOND CONTACTOR ENCLOSURE
6. LABEL CONTACTOR & TIME CLOCK
7. MEDIA CENTERS - FILL UNUSED OPENINGS & PROTECT CABLES ENTERING CENTERS.
11/27/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) ALL CEILING TILES TO BE REMOVED FOR CEILING INSPECTION EXCEPT THOSE TILES NEEDED TIO MOUNT EQUIPMENT
10/26/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER HARD LIDS/SOFFITS

NOTE: J-BOXES HAVE OFFICE AREA STILL TO BE COMPLETED