Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02790
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* AT PANELS WALL 1. INSTALL NAIL PLATE - NEC 300.4 2. INSTALL METAL K.O SEALS NEC 110 OK WALL COVER AFTER CORRECTIONS NOTE: CHECK MC BUNDLING IN CEILING - NEC 310.15 |
|
10/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR WALL COVER TIGHTEN ALL GROUND SCREWS, DON'T OVERFILL WIRE NUTS PROVIDE GFI PROTECTION FOR CONSTRUCTION POWER PANEL AREA WALLS NOT READY/DON'T COVER |
|
09/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DEMISING WALL ONLY |