Permit: T07CM02790

Parcel: 125076370

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02790

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
AT PANELS WALL

1. INSTALL NAIL PLATE - NEC 300.4
2. INSTALL METAL K.O SEALS NEC 110
OK WALL COVER AFTER CORRECTIONS

NOTE: CHECK MC BUNDLING IN CEILING - NEC 310.15
10/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALL COVER
TIGHTEN ALL GROUND SCREWS, DON'T OVERFILL WIRE NUTS
PROVIDE GFI PROTECTION FOR CONSTRUCTION POWER
PANEL AREA WALLS NOT READY/DON'T COVER
09/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DEMISING WALL ONLY