Permit: T07CM02787

Parcel: 125114970

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM02787

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/20/2007 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
11/16/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO FOLLOW ALL SHEAR/HOLDOWNS SCHEDULES PER PLANS
2) FOLLOW ALL APPROVED PLANS PER DETAILS
3) WARNING A REFEE WILL APPLY IF NOT READY AT NEXT INSPECTION
10/25/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING SCREWS AT EDGES ON DECK
2) NEED REVISIONS ON CHANGES WITH CITY APPROVALS
10/10/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN NUTS ON H/D'S MARKED ON FLOOR
2. NAIL OFF SHEAR WALLS PER PLANS AS MARKED IN BLACK CRAYON
3. H/D 7 REQUIRES 22-10d NAILS EACH STRAP W/2 STRAP
INTO 2 - 2X
4. NEED WIND BRACING 2ND FLOOR EAST END
5. H/D 6 REQUIRES 1 CS WITH 22-10d NAILS
6. COVERED DECK ROOFING ELEVATION 1 NOT 2
7. NEED ADDITIONAL FRAMING AT AC UNIT AREA - 4' X 7' AREA WITH NO SUPPORT