Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2008 | ELECTRIC - FINAL | Cancelled | ||
| 03/24/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/21/2008 | ELECTRIC - FINAL | Denied | 1) NEED PROPER WORKING CLEARANCE IN FRONT OF CONDENSING UNITS FOR DISCONNECTS 30" X 36" 2) CANNOT FEED THRU ONE DISCONNECT TO OTHER 3) HAVE MORE THAN ONE GROUND UNDER SINGLE TERMINATION IN DISCONNECTS 4) INSTALL EXTENSION RINGS ON SWITCH AND RECEPTACLE BASES MORE THAN 1/4" BACK FROM FINISHED SURFACE |