Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02781
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CIRCUITS NOT WIRED/LAYED OUT PER PLAN 2. PROVIDE GFI PROTECTION PER PLAN 3. PANEL DIRECTORIES NOT CORRECT 4. WATER HEATER J-BOX MISSING K.O SEAL, SELF-TAP SCREW NOT ALLOWED FOR GROUND, NEED MINIMUM #10 CU TO GROUND BOX 5. SECURELY MOUNT WATER HEATER DISCONNECT THERE WILL BE A FEE IF CORRECTIONS NOT COMPLETE NEXT INSPECTION! |
|
10/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY IDENTIFY CKT'S IN PANEL DIRECTORY NEC 408.4 2. MINIMUM #10 CU GROUND FOR 30 AMP WATER HEATER CKT NEC 250.122 3. HAVE PLANS AT LOUNGE FOR INSPECTION |