Permit: T07CM02781

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CIRCUITS NOT WIRED/LAYED OUT PER PLAN
2. PROVIDE GFI PROTECTION PER PLAN
3. PANEL DIRECTORIES NOT CORRECT
4. WATER HEATER J-BOX MISSING K.O SEAL, SELF-TAP SCREW
NOT ALLOWED FOR GROUND, NEED MINIMUM #10 CU TO GROUND BOX
5. SECURELY MOUNT WATER HEATER DISCONNECT

THERE WILL BE A FEE IF CORRECTIONS NOT
COMPLETE NEXT INSPECTION!
10/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY IDENTIFY CKT'S IN PANEL DIRECTORY
NEC 408.4
2. MINIMUM #10 CU GROUND FOR 30 AMP WATER HEATER CKT
NEC 250.122
3. HAVE PLANS AT LOUNGE FOR INSPECTION